| Features |
Performance |
Personnel
Safety / Resistance to ground (protection from electric shock)
|
> 7.5 x 105
Ohm |
Protection to 100V device sensitivity
(person to ground maximum resistance)
|
< 3.5 x 107
Ohm Tested at 100V |
Floor Surface to Ground Resistance /
Volume Resistivity * (typical average)
|
< 2.3 x 105 Ohm |
Maximum Surface Resistance
|
6.7 x 109 Ohm |
Charging of test subject during running
test
|
1.1 kV |
Product Guarantee
|
20 years |
Guarantee for ESD Performance
|
Lifetime |
| (* A conductive strip is
required to earth the tiles, one earth point required per 30m2 of floor area to be covered or one earth point per section of
tiles installed (which ever is the lower) |